Zone Cable U/FTP

10GCopper-Zone-Cable-U-FTP

Zone Cable U/FTP

10G COPPER – Zone Cable U/FTP – CAT6A SYSTEMS

Copperon Copper Cables – 10GCopper Zone Cable

Communication Cable, u/FtP, 100 Ω, 4x2xAWg 26/1

10GCopper U/FTP, 100 Ω, 4x2xAWG 23/1 is a premium grade Class EA / Augmented Category 6 cable to support 10 Gigabit Ethernet protocol for installation in horizontal and backbone areas.

PRODUCT PERFORMANCE:

Core

  • Conductor: 26 AWg Plain Annealed Copper Wire
  • Insulation: Cellular Polyolefin
  • Diameter: 1.0mm nominal
  • Pair: 2 of the above cores
  • Tape Screen: Individual pair wrapped with aluminium polyester tape, applied metal side out
  • Pair Colour: Blue-White, orange-White, Green-White, Brown-White

Final Assembly

  • Cable: 4 of the above shielded pairs
  • Braid Screen: 0.5mm tinned Annealed Copper Wire
  • Sheath: LSHF compound

Mechanical and Environmental

  • Temp – Installation: 0°c to +50°c
  • Temp – Operation: -20°c to +75°c
  • Max Tensile Load: 10kg per simplex cable (installation)
  • Min Bend Radius: 8 x Outer Diameter (installation) 4 x Outer Diameter (operation)
  • Halogen Free cable types (LSHF) meet IeC 60754-1 and IeC 61034

Product Specs

Electrical Characteristics @ 20°c Specification Typical Performance
Conductor Loop Resistance <29 Ω / 100m 26
Conductor resistance unbalance Max 2% 0.5%
Dielectric Strength 1.0kV dc or 0.7kV ac for 1 min 100% in process test
Insulation Resistance >500MΩ.km @ 100-500 V test voltage >5000m Ω/m
Capacitance unbalance to earth max. 160 pF/100m 60 pF/100m
Velocity of Propagation <537.6 nsec/100m @ 100MHz 417 nsec/100m @ 100mHz (nVP for hand held testers = 0.80)
Skew Max. 45 nsec/100m @ 100mHz 5 nsec/100m @ 1100mHz
mean Characteristic Impendance 100Ω+/-5Ω @ 100MHz 100 Ω +/-3Ω @100MHz
Characteristic Typical Headroom vs Cat6 (250MHz) Typical Headroom vs AC6 (500MHz)
Return Loss 5dB 5dB
Insertion Loss 20% 20%
NEXT 20dB 20dB
PSNEXT 20dB 20dB
ELFEXT 15dB 15dB
PSELFEXT 15dB 15dB
PSA ACR-N NA 20dB
PSAACR-F NA 20dB

Typical headroom on key S/N characteristics – for information only

  Typical Headroom vs Cat6 (250MHz) Typical Headroom vs AC6 (500MHz)
PSACR @ 500MHz NA 35dB
PSAACR-N* @ 500MHz NA 20dB

* Power Sum Attenuation to Alien Crosstalk (near end) ratio the Alien crosstalk performance of cables is assessed using a ‘6 round 1’ or ‘4 on a drum’ method.

Specifications may change without notice. Display Product Photos Shown are samples for viewing, not actual products.